คำตอบอย่างรวดเร็ว
Start with the design case, not a catalogue size. Record design flow, allowable pressure loss, design temperature and pressure, design life, fluid, route, fittings, and the applicable standard. Split the route into main, riser, and branch rows. DESO’s PP-RCT page lists a 20–160 mm range and several SDR options, but confirm the current SKU table, pressure-temperature basis, and certificate scope for the exact model before approval.
Why Does PP-RCT Pipe Sizing Start Before the RFQ?
An enquiry that says “DN50, PN20, hot water” gives a supplier a label, not a design case. Two offers can match it while differing in inside diameter, fitting range, pressure-temperature basis, documentation, or assumed duty. The result is a quotation that looks precise but cannot be approved.
This guide follows the decision sequence a buyer needs: capture the engineer’s basis, split the route into segments, screen a trial size, fix the product definition, send one complete schedule, and compare replies on like-for-like evidence. It helps you buy the calculated result; it does not replace the engineer’s hydraulic design or local code review.
Which Design Inputs Turn a Project Brief Into a Sizing Schedule?
PP-RCT pipe sizing needs enough information to reproduce the design condition on each line. At minimum, record fluid, design flow, allowable velocity, allowable pressure loss, design pressure, design temperature, design life, route length, fitting and valve assumptions, and the applicable standard. Add project location, destination market, and approval route.
Use consistent units and identify the calculation revision. Also record whether the duty is domestic hot water, closed hydronic heating, chilled water, or condenser water; those services can impose different operating profiles. A flow in m³/h and a pressure loss in kPa is actionable. A flow without units is not.
Use one row per hydraulic segment, not one project-wide summary. Each row should carry the segment ID, loads served, design flow, proposed outside diameter, SDR or S-series, pressure-temperature basis, allowable loss, and source calculation. Keep unresolved values visible. If the family is still open, compare the ช่วงท่อ PPR before fixing the schedule; this guide assumes PP-RCT is already under consideration.
How Should You Separate Main, Riser, and Branch Sizing?

PP-RCT pipe sizing does not use one building-wide flow for every line. Each segment has its own downstream demand, pressure constraint, and fitting exposure. That distinction is where many otherwise tidy enquiries fail.
Why Is the Main Sized From Its Downstream Demand?
The main carries the combined flow for the loads downstream of that specific main, after the project’s approved diversity and future-capacity rules. Connected load is not automatically simultaneous design flow. Check pressure loss through the route, fittings, and valves, plus the pressure required at the next downstream point. Record served loads, design flow and units, proposed outside diameter and series, allowable loss, and calculation revision. Ask the engineer whether pump head and velocity screening are already included.
Why Must a Riser Be Checked at Its Highest or Remotest Point?
A riser carries only the flow in that vertical section. Its case includes the floors or zones served, static pressure from elevation, friction and fitting losses, and the pressure required at the critical point. The highest point may govern static pressure; the most remote point may govern available pressure. Tall buildings may have separate pressure zones, so the pump-discharge condition may not represent the whole riser. Put the zone, elevation basis, design flow, critical-point pressure, and any pressure-reducing assumption in the schedule.
Why Is a Branch Not a Smaller Copy of the Main?
A branch serves a terminal unit, fixture group, or small cluster. Size it from that terminal demand, its own route, and its allowable pressure loss. Copying the main flow onto every branch is a common schedule error. Count the fittings, valves, and transitions the branch actually needs; a short, simple run and a long, congested run at the same flow do not have the same loss case. Record the terminal served, branch flow, fitting assumption, allowable drop, proposed size and series, and approved calculation reference.
Read the three segment types together before sending the schedule. A main can be correctly sized yet deliver insufficient pressure to a riser; a riser can be correct yet leave no allowance for branch losses. The schedule should expose those dependencies rather than hide them in one building total.
How Should You Screen a Candidate Size Without Redesigning the System?

Screen by inside diameter, not the nominal label. Outside diameter is fixed by the product family, but wall thickness changes the bore. A pipe described as DN50 in one series can therefore behave differently from another DN50 at the same flow.
Then compare velocity, pressure loss, and total installed cost as one package. A smaller bore may reduce material use but increase pump energy, noise sensitivity, or fitting loss. A larger bore may reduce friction but add weight, insulation, support demand, and space conflict. Use the engineer’s allowable velocity and pressure-loss criteria; do not accept a supplier’s universal rule as project approval. Use the HVAC and heating duty to frame the application, then verify the exact product data. A trial size is a proposal to test against the design case, not a final selection.
How Should You Read SDR, PN, and S-Series in a Quote?
SDR, PN, and an S-series designation answer different questions. SDR is a geometry ratio: outside diameter divided by wall thickness. An S-series label is a separate standardized series designation used in some pipe tables; quote it as the supplier’s table defines it rather than treating it as another word for PN. PN is a nominal pressure class under stated conditions. None of the three, read alone, proves the allowable pressure at your design temperature and life.
Ask for the model row that links outside diameter, wall series, PN basis, allowable pressure at temperature, design life, and standard. DESO’s PP-RCT product page lists 20–160 mm sizes, multiple SDR options, and PN10/PN12.5/PN16/PN20. Its HVAC and heating page lists PP-RCT as PN16–PN20. Those page-level lists conflict; neither is a universal DESO range. Require the current SKU/model table and written pressure-temperature confirmation for the exact item before you approve the quotation.
What Eight Fields Make a PP-RCT Pipe RFQ Complete?
Send one schedule that every supplier can price on the same basis. The eight fields below also give you an audit trail when replies differ.
- Project and standard. Location, application, destination market, applicable design or product standard, and local approval requirement.
- Pipe definition. Family, outside diameter, SDR or S-series, required PN or pressure-temperature basis, and whether equivalents are allowed.
- Hydraulic schedule. Design flow and calculated size for each main, riser, and branch row, with units and calculation revision.
- Duty. Fluid, design temperature and pressure, design life, operating profile, and any permitted excursion.
- System components. Fittings, valves, transitions, and installation tools by size and connection method. Use the ช่วงข้อต่อ PPR to check connection types, then confirm exact models.
- Evidence. Required test reports, certificates, drawings, marking, traceability, and submittal format.
- Commercial logistics. Quantity, packing, labelling, shipping terms, destination, delivery milestone, and import documents.
- Customization. Colour, branding, packaging, private-label artwork, and approval criteria. DESO’s OEM and private-label page describes customization services; confirm feasibility and commercial terms in writing for your item.
Mark every field the supplier cannot confirm. A quotation that leaves an unresolved pressure basis or certificate scope blank is more useful than one that fills it with an assumption. A complete PP-RCT pipe sizing enquiry should also name who owns the hydraulic calculation and which revision the supplier must quote.

How Should You Compare Quotations Before You Approve One?
Compare the quoted basis, not the headline price. Put each offer into the same matrix and state differences in the supplier’s own words. Do not treat an assumed equivalent as a like-for-like offer. Record the supplier’s basis beside your required basis; use written clarifications to close gaps, not verbal assumptions.
- Identity: model, outside diameter, SDR or S-series, and dimensions match the schedule.
- Hydraulic basis: quoted size and allowable pressure loss match the approved calculation revision.
- Duty: the pressure-temperature row covers fluid, design temperature, pressure, and design life.
- Components: fittings, valves, transitions, and tools match the pipe and joining method.
- Evidence: SKU sheet, pressure-temperature table, certificate scope, test reports, drawings, marking, and traceability meet the required submittal.
- Commercial scope: quantity, packing, labelling, shipping basis, delivery milestone, and customization are stated on the same line.
เดโซ quality-inspection page describes batch testing and inspection, and its manufacturing page describes production and product marking. Treat both as first-party process descriptions: ask which checks and records apply to your order, and how the shipment marking links to its batch record. A certificate list is not a model map. Leave price out of the decision until the technical and evidence columns align; the lowest pipe price can lose once missing fittings, rework, or an unapproved submittal are added.
What Three Buyer Questions Should You Settle Before Approval?
Can You Size PP-RCT Pipe From Flow Rate Alone?
No. Flow is one input. You also need allowable pressure loss, route length and fittings, fluid, design temperature, design pressure, design life, applicable standard, and the exact SDR or series. A supplier can suggest a trial size from a complete brief, but the engineer’s calculation governs final selection.
Is a Larger Pipe Always Safer?
No. A larger bore can reduce velocity and friction, but it may add material, weight, insulation, support, and space cost. It can also move operating velocity away from the intended range. Compare total installed cost and the design pressure-loss target, not size alone, and ask the engineer to confirm the margin.
Does a Certificate Cover Every PP-RCT Size?
Do not assume so. Check the certificate holder, standard, validity, scope, covered product models, and acceptance in the destination market. A website certificate list is not a certificate-to-SKU map. Request the certificate and scope for the exact size and order.
What Should You Send With the Final Enquiry?
A complete PP-RCT pipe sizing package lets the supplier quote the actual product instead of guessing. Send the segment schedule for main, riser, and branch; project conditions including fluid, design flow, allowable pressure loss, temperature, pressure, design life, and applicable standard; exact outside diameter and SDR or S-series; required PN or pressure-temperature basis; fittings, valves, and tools; destination market; quantity and packing; and any customization request.
Add the evidence package needed to review the quotation: current SKU sheet, written pressure-temperature confirmation, certificate and scope for the exact model, applicable test reports and drawings, marking and traceability details, and the required submittal format. Ask DESO to mark any item it cannot confirm and to quote against the named calculation revision.
That package makes the next reply auditable. A nominal size and a price request are not enough; the conditions and evidence are what make the size defensible.